Contact
Applications
CU/XLPE/PVC cables are used for electricity supply in low voltage installation system, they are suitable for:
· installation in indoors and outdoors
· in cable ducts
· under ground
· in power and switching stations
· local energy distributions
· industrial plants
where there is no risk of mechanical damage.
For any more information or advice please contact the office on 0086-18832134509(WhatsApp/WeChat)
Details
Description: N2XY, XLPE Insulated Copper Power Cable
Conductors:Class 1 or Class 2 of plain copper,or of Class 5 of plain copper in accordance with IEC 60228.
Insulation:Cross-linked polyethylene XLPE
Insulation Colour:Natural or as required
Filler: Non-hygroscopic Material
Outer Sheath:Extruded Polyvinyl Chloride PVC&Polyethylene PE&LSZH
Colour of Sheath: Black
Voltage Rating (Uo/U):600/1000V Test Voltage: 3.5kV for 5 minutes
Physical Properties
Maximal operating conductor Temperature: up to 70℃(PVC insulation); up to 90℃(XLPE insulation)
Operating Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)
Short Circuit Temperature(5 seconds maximum duration): 140℃-160℃(PVC insulation);250℃(XLPE insulation)
Technical Data
0.6/1kV-2 core copper conductor XLPE insulated PVC sheathed power cable | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
(mm2) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
2X1.5 | 0.7 | 1.8 | 10.4 | 105 | 12.1 | 24 | 35 |
2X2.5 | 0.7 | 1.8 | 11.2 | 135 | 7.41 | 33 | 46 |
2X4 | 0.7 | 1.8 | 12.2 | 175 | 4.61 | 43 | 59 |
2X6 | 0.7 | 1.8 | 13.2 | 230 | 3.08 | 55 | 75 |
2X10 | 0.7 | 1.8 | 15.4 | 340 | 1.83 | 76 | 100 |
2X16 | 0.7 | 1.8 | 17.4 | 480 | 1.15 | 97 | 130 |
2X25 | 0.9 | 1.8 | 20.5 | 700 | 0.727 | 130 | 165 |
2X35 | 0.9 | 1.8 | 22.5 | 930 | 0.524 | 160 | 200 |
2X50 | 1.0 | 1.8 | 20.3 | 1000 | 0.387 | 195 | 240 |
2X70 | 1.1 | 1.8 | 23.3 | 1400 | 0.268 | 245 | 290 |
2X95 | 1.1 | 1.9 | 26.2 | 1950 | 0.193 | 305 | 355 |
2X120 | 1.2 | 2.0 | 29.4 | 2450 | 0.153 | 355 | 405 |
2X150 | 1.4 | 2.2 | 32.6 | 3000 | 0.124 | 405 | 450 |
2X185 | 1.6 | 2.3 | 36.0 | 3700 | 0.0991 | 465 | 510 |
0.6/1kV-3 core copper conductor XLPE insulated PVC sheathed power cable | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
(mm2) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
3X1.5 | 0.7 | 1.8 | 11.8 | 135 | 12.1 | 21 | 30 |
3X2.5 | 0.7 | 1.8 | 12.7 | 180 | 7.41 | 28 | 39 |
3X4 | 0.7 | 1.8 | 13.8 | 225 | 4.61 | 37 | 51 |
3X6 | 0.7 | 1.8 | 14.9 | 300 | 3.08 | 47 | 64 |
3X10 | 0.7 | 1.8 | 17.2 | 430 | 1.83 | 65 | 86 |
3X16 | 0.7 | 1.8 | 19.4 | 630 | 1.15 | 84 | 110 |
3X25 | 0.9 | 1.8 | 22.8 | 940 | 0.727 | 110 | 140 |
3X35 | 0.9 | 1.8 | 25.0 | 1250 | 0.524 | 135 | 170 |
3X50 | 1.0 | 1.8 | 24.4 | 1500 | 0.387 | 170 | 205 |
3X70 | 1.1 | 1.9 | 29.4 | 2140 | 0.268 | 215 | 250 |
3X95 | 1.1 | 2.0 | 33.6 | 2960 | 0.193 | 265 | 300 |
3X120 | 1.2 | 2.1 | 35.9 | 3760 | 0.153 | 310 | 345 |
3X150 | 1.4 | 2.3 | 39.9 | 4420 | 0.124 | 350 | 385 |
3X185 | 1.6 | 2.4 | 44.1 | 5950 | 0.0991 | 405 | 435 |
3X240 | 1.7 | 2.6 | 51.1 | 7100 | 0.0754 | 480 | 500 |
3X300 | 1.8 | 2.7 | 56.1 | 9000 | 0.0601 | 555 | 565 |
3X400 | 2.0 | 3.0 | 62.4 | 10000 | 0.0470 | 640 | 640 |
0.6/1kV-4 core copper conductor XLPE insulated PVC sheathed power cable | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
(mm2) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
4X1.5 | 0.7 | 1.8 | 12.6 | 160 | 12.1 | 21 | 30 |
4X2.5 | 0.7 | 1.8 | 13.6 | 210 | 7.41 | 28 | 39 |
4X4 | 0.7 | 1.8 | 14.8 | 280 | 4.61 | 37 | 51 |
4X6 | 0.7 | 1.8 | 16.0 | 380 | 3.08 | 47 | 64 |
4X10 | 0.7 | 1.8 | 18.6 | 530 | 1.83 | 65 | 86 |
4X16 | 0.7 | 1.8 | 21.0 | 800 | 1.15 | 84 | 110 |
4X25 | 0.9 | 1.8 | 24.9 | 1240 | 0.727 | 110 | 140 |
4X35 | 0.9 | 1.8 | 28.3 | 1600 | 0.524 | 135 | 170 |
4X50 | 1.0 | 1.8 | 28.4 | 2000 | 0.387 | 170 | 205 |
4X70 | 1.1 | 2.0 | 33.1 | 2800 | 0.268 | 215 | 250 |
4X95 | 1.1 | 2.1 | 37.1 | 4000 | 0.193 | 265 | 300 |
4X120 | 1.2 | 2.2 | 40.8 | 5000 | 0.153 | 310 | 345 |
4X150 | 1.4 | 2.4 | 45.2 | 6100 | 0.124 | 350 | 385 |
4X185 | 1.6 | 2.6 | 52.1 | 7600 | 0.0991 | 405 | 435 |
4X240 | 1.7 | 2.8 | 57.8 | 9500 | 0.0754 | 480 | 500 |
4X300 | 1.8 | 3.0 | 63.5 | 12000 | 0.0601 | 555 | 565 |
4X400 | 2.0 | 3.3 | 70.9 | 16000 | 0.0470 | 640 | 640 |
0.6/1kV-5 core copper conductor XLPE insulated PVC sheathed power cable | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
(mm2) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
5X1.5 | 0.7 | 1.8 | 11.7 | 170 | 12.1 | 21 | 30 |
5X2.5 | 0.7 | 1.8 | 12.8 | 250 | 7.41 | 28 | 39 |
5X4 | 0.7 | 1.8 | 14.0 | 330 | 4.61 | 37 | 51 |
5X6 | 0.7 | 1.8 | 15.4 | 460 | 3.08 | 47 | 64 |
5X10 | 0.7 | 1.8 | 18.8 | 700 | 1.83 | 65 | 86 |
5X16 | 0.7 | 1.8 | 21.8 | 1000 | 1.15 | 84 | 110 |
5X25 | 0.9 | 1.8 | 26.2 | 1540 | 0.727 | 110 | 140 |
5X35 | 0.9 | 1.8 | 28.0 | 2080 | 0.524 | 135 | 170 |
5X50 | 1.0 | 1.9 | 32.4 | 2760 | 0.387 | 170 | 205 |
5X70 | 1.1 | 2.1 | 37.4 | 3890 | 0.268 | 215 | 250 |
5X95 | 1.1 | 2.2 | 41.7 | 5120 | 0.193 | 265 | 300 |
5X120 | 1.2 | 2.4 | 46.2 | 6530 | 0.153 | 310 | 345 |
5X150 | 1.4 | 2.6 | 53.1 | 8000 | 0.124 | 350 | 385 |
5X185 | 1.6 | 2.8 | 58.9 | 9800 | 0.0991 | 405 | 435 |
5X240 | 1.7 | 3.0 | 65.6 | 12400 | 0.0754 | 480 | 500 |
5X300 | 1.8 | 3.2 | 72.0 | 15450 | 0.0601 | 555 | 565 |